9.2.1. 30min WindMax High
Message ID: 3
Triggers when: The 30 minute maximum wind is greater or equal 35km/h
and
the antenna servo state is not stowed.
This message alerts the observer to strong winds and the possibility of a wind
stow.
9.2.2. Telescope idle and not stowed
Message ID: 4
Triggers when: Idle or drive_error time exceeds 5 minutes while at an
elevation of less than 84 degrees.
Alerts the observer to stow the telescope, or to initiate action to resolve the drive
error condition preventing the telescope from stowing.
9.2.3. Generator is running
Message ID: 11
Triggers when: Generator is running and lightning threat level equals 0
The generator should not normally run, only when the lightning threat level is
significant . This message can be indicative of a mains power failure.
9.2.4. Some lightning activity
Message ID: 12
Triggers when: Generator is not running and lightning threat level is
greater than 1
This alerts the observer to keep an eye on the weather. The generator does not
need to be started (yet).
9.2.5. Heavy lightning activity nearby
Message ID: 13
Triggers when: Lightning threat level equals 3 and the telescope is not
stowed.
Alerts the user to a potentially impending storm stow.
9.2.6. ACC in local mode
Message ID: 17